Signaline LocatorPlus

Stock Code: CSSIGLP001

Signaline SLP-001 LocatorPlus FT Dual Zone Distance Locator and Monitor

The Signaline SLP-001 LocatorPlus is a combined distance locator and monitoring module designed for use with all Signaline FT and FT-R linear heat detection cables.

UL-approved, the LocatorPlus provides instant identification of the alarm location along the Signaline FT linear heat detection cable. Unlike earlier locator devices, it can also remotely transmit the alarm location via MODBUS output. The unit supports two independent detection zones, each accommodating up to 3000 metres of Signaline FT cable.

In addition to precise location reporting, the LocatorPlus functions as a comprehensive monitoring module, detecting and reporting both fire and fault conditions on either zone. Alarm and fault statuses are clearly indicated by an internal buzzer and LED indicators on the unit.

The LocatorPlus is compatible with conventional fire alarm panels, can operate via an addressable interface, and may also be used as an activation device for gas extinguishing control panels.

Two operating modes are available:

  • Independent Mode – each zone reports alarms separately.

  • Interlocking Mode – alarm relays activate only when both zones are in alarm, reducing the risk of false activations.


Key Features & Technical Specifications

  • Model: Signaline LocatorPlus (SLP-001)

  • Dimensions: 180 × 120 × 60.5mm (H × W × D)

  • IP Rating: IP65

  • Finish: Light grey enclosure with clear lid

  • Display: 2-line, 16-character backlit LCD showing zone status

  • Approvals: UL 864, 10th Edition

Electrical

  • Operating Voltage: 12–36V DC

  • Operating Current: <12mA / <4mA

  • Alarm Current: <40mA / <15mA

  • Operating Temperature: -20°C to +50°C (-4°F to +122°F)

Wiring & Terminals

  • Terminal Blocks: 5mm spacing, rising clamp

  • Rated Current: 16A

  • Wire Size: 0.08mm² (28 AWG) to 4mm² (11 AWG)

  • Supervised Circuits: Power, Zone 1 input, Zone 2 input

Detection Zones

  • Inputs: Up to two zones of Signaline FT or FT-R linear heat detection

  • Zone Length: 1–3000m (10,000 ft) per zone

  • End-of-Line Resistor: 1kΩ (supplied)

  • Short-Circuit Current: 0.5mA

  • Maximum Voltage: 5V

  • Ground Fault Impedance:

Communications

  • Interface: Two-wire RS-485 Modbus RTU
    (Field wiring limited to the same room to comply with UL listing)

Indicators & Outputs

  • Sounder: 2.4kHz buzzer, 92dBA @ 10cm

Alarm Outputs

  • Relays: 2 × Form C volt-free contacts (resistive, common)

  • Maximum Voltage: 30Vac or 42.4Vdc

  • Maximum Current: 2A

  • Maximum Switching Power: 60W / 62.5VA

Fault Outputs

  • Type: 2 × opto-isolated phototransistor outputs (resistive, common)

  • Maximum Voltage: 35Vdc

  • Maximum Current: 80mA

  • Maximum Power Dissipation: 150mW