The Sigma CP range comprises a series of conventional fire alarm control panels designed and manufactured in compliance with European Standards BS EN54-2 and BS EN54-4 for Fire Detection and Fire Alarm Systems – Control and Indicating Equipment. The range is available in 2, 4, and 8 zone configurations.
All control panels are offered in two variants:
Sigma K11 range – Detectors and manual call points are wired on separate circuits from the sounders, with two dedicated sounder circuits provided.
Sigma T11 range – Detectors, manual call points, and sounders are connected on the same pair of cables, commonly known as a two-wire system. By wiring sounders onto the detection circuits, the need for separate sounder cabling is removed, while also enabling zoned or two-stage sounder operation (T-series only).
All panels incorporate an integral, mains-powered power supply and battery charger, designed in accordance with the requirements of BS EN54-4.
Key Features
Fully certified to BS EN54-2 and BS EN54-4
Available in 2-wire and standard versions with 2, 4, or 8 zones
Suitable for use on BS5839-1:2002 compliant installations
Support for 2-wire repeaters and ancillary expansion boards
Simple single-board construction
Installer-friendly design
Compatible with a wide range of detection devices
Two monitored sounder outputs
3 Amp power supply
Auxiliary power output
Fully Programmable via Simple Menu Options
Adjustable sounder delay times
Sounder configuration options
Zonal sounder delay for detectors only
Zonal sounder delay for call points only
Coincidence input selection
I.S. barrier selection by zone
Short-circuit fire indication by zone
Non-latching zone options
Silent zones
Zone input delays
General panel configuration
Dimensions
385mm W x 310mm H x 90mm D