Twinflex Pro2 4 Zone Control Panel

Stock Code: FK505-0004

The TwinflexPro2 is an intelligent 2-wire fire alarm control panel that uses a conventional-style cabling format. Due to its system architecture, it is classified as analogue non-addressable, with field devices communicating with the control panel via the Twinflex data protocol.

Available in 2, 4, and 8 zone variants, the TwinflexPro2 supports up to 32 Twinflex devices per zone. The panel can identify and distinguish between alarms from smoke detectors, heat detectors, and manual call points, providing clearer alarm information and faster response.

System Monitoring & Outputs

Each zone is continuously monitored for detector head removal, device faults, end-of-line (EOL) faults, and open or short circuit conditions.

The panel provides:

  • 2 × monitored outputs configurable as conventional sounder circuits

  • 1 × volt-free common fire relay

  • 1 × volt-free common fault relay

  • 2 × multifunction latching/non-latching inputs

  • 1 × monitored input programmable for functions such as Class Change and Remote Fire

An integral power supply is included, requiring 2 × 12V 3.2Ah batteries to provide up to 72 hours standby time.

Configuration & Flexibility

The TwinflexPro2 features a 500-event log, day/night mode, alarm confirmation, and programmable alarm delays. Configuration can be carried out via the on-board keypad or through PC-driven OSP software.

Originally compatible only with Fike Twinflex devices, the system now offers greater flexibility. With the addition of a conventional zone card, 4 and 8 zone panels can be configured to accept conventional devices on zones 5 to 8.

Simplified Wiring

Unlike most conventional fire alarm systems that require separate wiring for detector zones and sounder circuits, the Twinflex system uses a single 2-core screened cable per zone. This allows both detection devices and sounders to operate on the same circuit when Twinflex devices are used, significantly reducing installation time and cabling requirements.


Key Features

  • 4-line × 20-character LCD display

  • Differentiates between smoke detector, heat detector, and manual call point alarms

  • Alarm confirmation facility

  • Available in 2, 4, and 8 zone versions

  • RS485 connection for up to 8 repeater panels

  • Highlighted menu navigation

  • Event log capacity of up to 500 events

  • 3 enhanced test modes

  • Detection devices and sounders on the same pair of wires

  • Supports up to 32 devices per zone

  • Built-in end-of-line capability in all devices

  • 7 selectable detection modes

  • Configurable day/night zone operation

  • Programmable alarm delays

Dimensions

331mm W x 331mm H x 99mm D

Max. No. Zone4
Panel typeTwinFlex
Max. Battery Capacity3.2Ah - 12v